Control Transformer Sizing

Stop recalculating transformer VA and fuse sizes every time the control load changes.

Change the load or voltage and the system updates transformer size, calculated currents, protection, and generated data automatically. LogiDraft applies rule-driven sizing so the schematic and generated data stay in sync.

Change control load or voltage and watch transformer size and fuse protection update instantly.

Primary Voltage240 or 480 V
Control Voltage24 or 120 V
Sizing RuleRequired VA = load x 1.25
Lookup OutputTransformer + fuse selection

Automatic transformer sizing and protection

This sizing result is generated directly from the same logic used in the workspace.

  • At 50 VA load: 75 VA transformer, 1 A primary fuse, 5 A secondary fuse.
  • At 500 VA load: 750 VA transformer, 5 A primary fuse, 50 A secondary fuse.

Change load or voltage and the sizing updates automatically.

Control Load: 50 VA
Control Transformer Sizing example showing a 75 VA transformer with 1 A primary fuse for a 50 VA control load
Control Load: 500 VA
Control Transformer Sizing example showing a 750 VA transformer with 5 A primary fuse for a 500 VA control load

Increasing load steps transformer size from 75 VA to 750 VA and scales fuse protection automatically.

Change inputs in the workspace and this result updates automatically.

These changes are reflected directly in structured output data.

Control Load (VA)Transformer (VA)Primary Fuse (A)Secondary Fuse (A)
507515
500750550

Geometry and data stay aligned because they are generated from the same logic.

Inputs and outputs

Control load and voltage resolve the transformer selection, calculated currents, and protection values together.

Inputs

  • Primary voltage
  • Control voltage
  • Control load

Outputs

  • Transformer VA
  • Primary and secondary currents
  • Primary and secondary fuse sizing

Rule-driven sizing logic

The sizing logic follows standard electrical calculations, encoded directly in the model.

Calculation flow

  1. Calculate required VA as control load multiplied by 1.25.
  2. Select the next standard transformer size with lookup logic.
  3. Calculate primary current from transformer VA and primary voltage.
  4. Calculate secondary current from transformer VA and control voltage.
  5. Select primary and secondary fuse sizes from standard ratings.

Standard ratings

The example uses standard fuse sizes of 1, 2, 3, 5, 10, 15, 20, 30, and 50 A. Fuse protection is selected by rounding each calculated current up to the next available standard rating.

Because the calculations are encoded directly in the model, the transformer symbol and both fuse symbols stay aligned with the resolved values without extra manual checking.

Outputs

The resolved transformer produces usable engineering data that can be exported and kept aligned with the visible sizing result.

Required VA, transformer size, currents, and fuse values are available as generated data from the same evaluated model.

Exported data stays aligned with the schematic, so schedules and downstream checks can use the same resolved values.

Outputs50 VA load sample
CSV / JSON
Required VA62.5
Transformer Size (VA)75
Primary Current (A)0.31
Secondary Current (A)3.13
Primary Fuse (A)1
Secondary Fuse (A)5

Manual sizing versus LogiDraft

Transformer sizing is repetitive work. Encoding it once keeps the calculation, the schematic, and the generated data aligned.

Manual workflow

Calculate, round, then redraw

  • Apply the safety factor by hand.
  • Pick the next standard transformer size manually.
  • Recalculate currents for every voltage change.
  • Choose standard fuse ratings separately from the schematic.
LogiDraft workflow

One rule set drives the result

  • The sizing factor is applied consistently every time.
  • The transformer VA comes from the defined standard-size lookup.
  • Current and fuse calculations stay tied to the same resolved values.
  • The drawing and the structured output remain correct together.

Use this example

How this works

Open the example and change inputs to see the system update

Open this and change one value - you'll immediately see how the system works.

Open this example and:

  • Change control load or voltage
  • Watch transformer size, currents, and fuse sizing update automatically

Related parametric panel workflows

Control transformer sizing is a focused example of inputs, lookup tables, drawing updates, and output data staying connected.

Parametric electrical CAD

See how inputs, formulas, lookup tables, reusable definitions, drawings, and outputs fit together as a category.

Read the parametric CAD guide

Control panel design software

Learn how control transformer logic fits into broader control panel workflows with schematic and BOM coordination.

Read the panel workflow guide

Reference

Exact lookup function syntax.